STORMWATER FACILITY
2010 BRUSHY CREEK RD RD BRUSHY CREEK RD
Greenville County · South Carolina
Condition describes the latest dated source assessment available, not a verified present-day assessment.
| Date | Record | Condition / result | Repairs & notes | Evidence |
|---|---|---|---|---|
| Dec 7, 2015 | InspectionGC Re-Inspection | Acceptable | Not recorded | Greenville County public stormwater BMP GIS |
| Nov 25, 2015 | InspectionGC Re-Inspection | Unacceptable | Priority 1: Stabilize at Outlet Priority 2: WORK DONE. CALLED CONTRACTOR. ITS TO WET TO WORK. | Greenville County public stormwater BMP GIS |
| Sep 30, 2015 | InspectionGC Re-Inspection | Unacceptable | Priority 1: Repair Structural Damage to Riser Priority 2: RISER OR OUTLET STRUCTURE STILL NEEDS TO BE REPLACE. WILL SEND NEXTS NOV. SENT 10.01.2015 | Greenville County public stormwater BMP GIS |
| Aug 28, 2015 | InspectionGC Re-Inspection | Unacceptable | Priority 1: Stabilize at Outlet Priority 2: VEG. MAINT. COMPLETED. NEED TO REPAIR OUTLET PIPE. | Greenville County public stormwater BMP GIS |
| Jul 28, 2015 | InspectionGC Re-Inspection | Unacceptable | Priority 1: Repair Structural Damage to Riser Priority 2: RIP RAP CHANNEL HAS BEEN CLEARED OF ALL VEGETATION. NEED TO REPAIR DAMAGE TO INLET PIPE/ RISER. WORK WILL BEGAIN NEXTS WEEK. | Greenville County public stormwater BMP GIS |
| Jul 20, 2015 | InspectionGC Re-Inspection | Unacceptable | Priority 1: Clean Out Trash , Cut Back/Clean Up Overgrown Vegetation , Repair Structural Damage to Inlet(s) Priority 2: NO CHANGE FROM PREVIOUS INSPECTION. CALLED MAINT. MANAGER WORK SHOULD START THURSDAY. | Greenville County public stormwater BMP GIS |
| Jun 22, 2015 | InspectionGC Re-Inspection | Unacceptable | Priority 1: Repair Structural Damage to Riser , Cut Back/Clean Up Overgrown Vegetation , Remove Large Woody Vegetation Priority 2: NO CHANGE FROM PREVIOUS INSPECTION. WILL SEND NEXT NOV. | Greenville County public stormwater BMP GIS |
| May 20, 2015 | InspectionInitial Inventory | Unacceptable | Priority 1: Cut Back/Clean Up Overgrown Vegetation , Stabilize at Outlet Priority 2: RIP RAP CHANNEL OVERGROWN. CANNOT FIND OUTLET PIPE ONLY A HOLE IN GROUND WILL HAVE TO LOOK AT PLANS. SENT NOV 06.02.2015 | Greenville County public stormwater BMP GIS |
Published inspection recommendations are shown with their dates. The database does not establish whether these repairs remain unresolved.
Priority 1: Stabilize at Outlet
Priority 2: WORK DONE. CALLED CONTRACTOR. ITS TO WET TO WORK.
Priority 1: Repair Structural Damage to Riser
Priority 2: RISER OR OUTLET STRUCTURE STILL NEEDS TO BE REPLACE. WILL SEND NEXTS NOV. SENT 10.01.2015
Priority 1: Stabilize at Outlet
Priority 2: VEG. MAINT. COMPLETED. NEED TO REPAIR OUTLET PIPE.
Priority 1: Repair Structural Damage to Riser
Priority 2: RIP RAP CHANNEL HAS BEEN CLEARED OF ALL VEGETATION. NEED TO REPAIR DAMAGE TO INLET PIPE/ RISER. WORK WILL BEGAIN NEXTS WEEK.
Priority 1: Clean Out Trash , Cut Back/Clean Up Overgrown Vegetation , Repair Structural Damage to Inlet(s)
Priority 2: NO CHANGE FROM PREVIOUS INSPECTION. CALLED MAINT. MANAGER WORK SHOULD START THURSDAY.
Priority 1: Repair Structural Damage to Riser , Cut Back/Clean Up Overgrown Vegetation , Remove Large Woody Vegetation
Priority 2: NO CHANGE FROM PREVIOUS INSPECTION. WILL SEND NEXT NOV.
Priority 1: Cut Back/Clean Up Overgrown Vegetation , Stabilize at Outlet
Recorded condition: Source score: 100
Review supporting evidence →Recorded condition: Acceptable
Review supporting evidence →Recorded condition: Unacceptable · Repair recommendations recorded
Review supporting evidence →Recorded condition: Unacceptable · Repair recommendations recorded
Review supporting evidence →Recorded condition: Unacceptable · Repair recommendations recorded
Review supporting evidence →Recorded condition: Unacceptable · Repair recommendations recorded
Review supporting evidence →Recorded condition: Unacceptable · Repair recommendations recorded
Review supporting evidence →Recorded condition: Unacceptable · Repair recommendations recorded
Review supporting evidence →Recorded condition: Unacceptable · Repair recommendations recorded
Review supporting evidence →Published values appear beside the database value. Retrieval time records when evidence was collected; it is not an inspection or source-update date.
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 2242 | 2242 |
| Legacy Asset Id | 2822 | 2822 |
| Parcel Id | 0538050100401 | 0538050100401 |
| Address | 2010 BRUSHY CREEK RD RD BRUSHY CREEK RD | 2010 BRUSHY CREEK RD RD BRUSHY CREEK RD |
| Source facility type | Dry Detention Pond | Dry Detention Pond |
| Site Name | AHC STERLING HOUSE GREENVILLE | AHC STERLING HOUSE GREENVILLE |
| Responsible party | AHC STERLING HOUSE GREENVILLE | AHC STERLING HOUSE GREENVILLE |
| Condition Date | 2022-02-04T14:46:23.000Z | 1643985983000 |
| Source condition score | 100 | 100 |
Priority 2: RIP RAP CHANNEL OVERGROWN. CANNOT FIND OUTLET PIPE ONLY A HOLE IN GROUND WILL HAVE TO LOOK AT PLANS. SENT NOV 06.02.2015
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 2234 | 2234 |
| Legacy Asset Id | 2822 | 2822 |
| Source facility type | Dry Detention Pond | Dry Detention Pond |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 3189 | 3189 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-06-22T13:30:45.000Z | 1434979845000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Repair Structural Damage to Riser , Cut Back/Clean Up Overgrown Vegetation , Remove Large Woody Vegetation | Repair Structural Damage to Riser , Cut Back/Clean Up Overgrown Vegetation , Remove Large Woody Vegetation |
| Priority 2 repair recommendations | NO CHANGE FROM PREVIOUS INSPECTION. WILL SEND NEXT NOV. | NO CHANGE FROM PREVIOUS INSPECTION. WILL SEND NEXT NOV. |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 3233 | 3233 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-07-28T13:54:14.000Z | 1438091654000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Repair Structural Damage to Riser | Repair Structural Damage to Riser |
| Priority 2 repair recommendations | RIP RAP CHANNEL HAS BEEN CLEARED OF ALL VEGETATION. NEED TO REPAIR DAMAGE TO INLET PIPE/ RISER. WORK WILL BEGAIN NEXTS WEEK. | RIP RAP CHANNEL HAS BEEN CLEARED OF ALL VEGETATION. NEED TO REPAIR DAMAGE TO INLET PIPE/ RISER. WORK WILL BEGAIN NEXTS WEEK. |
| Vegetation Condition | Yes | Yes |
| Trash Condition | Yes | Yes |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 5370 | 5370 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-05-20T12:29:53.000Z | 1432124993000 |
| Inspection Type | Initial Inventory | Initial Inventory |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Cut Back/Clean Up Overgrown Vegetation , Stabilize at Outlet | Cut Back/Clean Up Overgrown Vegetation , Stabilize at Outlet |
| Priority 2 repair recommendations | RIP RAP CHANNEL OVERGROWN. CANNOT FIND OUTLET PIPE ONLY A HOLE IN GROUND WILL HAVE TO LOOK AT PLANS. SENT NOV 06.02.2015 | RIP RAP CHANNEL OVERGROWN. CANNOT FIND OUTLET PIPE ONLY A HOLE IN GROUND WILL HAVE TO LOOK AT PLANS. SENT NOV 06.02.2015 |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 5386 | 5386 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-09-30T13:14:57.000Z | 1443618897000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Repair Structural Damage to Riser | Repair Structural Damage to Riser |
| Priority 2 repair recommendations | RISER OR OUTLET STRUCTURE STILL NEEDS TO BE REPLACE. WILL SEND NEXTS NOV. SENT 10.01.2015 | RISER OR OUTLET STRUCTURE STILL NEEDS TO BE REPLACE. WILL SEND NEXTS NOV. SENT 10.01.2015 |
| Vegetation Condition | Yes | Yes |
| Trash Condition | Yes | Yes |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 5619 | 5619 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-07-20T15:04:25.000Z | 1437404665000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Clean Out Trash , Cut Back/Clean Up Overgrown Vegetation , Repair Structural Damage to Inlet(s) | Clean Out Trash , Cut Back/Clean Up Overgrown Vegetation , Repair Structural Damage to Inlet(s) |
| Priority 2 repair recommendations | NO CHANGE FROM PREVIOUS INSPECTION. CALLED MAINT. MANAGER WORK SHOULD START THURSDAY. | NO CHANGE FROM PREVIOUS INSPECTION. CALLED MAINT. MANAGER WORK SHOULD START THURSDAY. |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 5770 | 5770 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-08-28T10:05:42.000Z | 1440756342000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Stabilize at Outlet | Stabilize at Outlet |
| Priority 2 repair recommendations | VEG. MAINT. COMPLETED. NEED TO REPAIR OUTLET PIPE. | VEG. MAINT. COMPLETED. NEED TO REPAIR OUTLET PIPE. |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 6038 | 6038 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-11-25T10:47:24.000Z | 1448448444000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Stabilize at Outlet | Stabilize at Outlet |
| Priority 2 repair recommendations | WORK DONE. CALLED CONTRACTOR. ITS TO WET TO WORK. | WORK DONE. CALLED CONTRACTOR. ITS TO WET TO WORK. |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 6054 | 6054 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-12-07T15:08:19.000Z | 1449500899000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Acceptable | Acceptable |
| Vegetation Condition | Yes | Yes |
| Sediment Condition | Yes | Yes |
| Trash Condition | Yes | Yes |
| Outlet Condition | Yes | Yes |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 3189 | 3189 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-06-22T13:30:45.000Z | 1434979845000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Repair Structural Damage to Riser , Cut Back/Clean Up Overgrown Vegetation , Remove Large Woody Vegetation | Repair Structural Damage to Riser , Cut Back/Clean Up Overgrown Vegetation , Remove Large Woody Vegetation |
| Priority 2 repair recommendations | NO CHANGE FROM PREVIOUS INSPECTION. WILL SEND NEXT NOV. | NO CHANGE FROM PREVIOUS INSPECTION. WILL SEND NEXT NOV. |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 3233 | 3233 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-07-28T13:54:14.000Z | 1438091654000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Repair Structural Damage to Riser | Repair Structural Damage to Riser |
| Priority 2 repair recommendations | RIP RAP CHANNEL HAS BEEN CLEARED OF ALL VEGETATION. NEED TO REPAIR DAMAGE TO INLET PIPE/ RISER. WORK WILL BEGAIN NEXTS WEEK. | RIP RAP CHANNEL HAS BEEN CLEARED OF ALL VEGETATION. NEED TO REPAIR DAMAGE TO INLET PIPE/ RISER. WORK WILL BEGAIN NEXTS WEEK. |
| Vegetation Condition | Yes | Yes |
| Trash Condition | Yes | Yes |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 5370 | 5370 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-05-20T12:29:53.000Z | 1432124993000 |
| Inspection Type | Initial Inventory | Initial Inventory |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Cut Back/Clean Up Overgrown Vegetation , Stabilize at Outlet | Cut Back/Clean Up Overgrown Vegetation , Stabilize at Outlet |
| Priority 2 repair recommendations | RIP RAP CHANNEL OVERGROWN. CANNOT FIND OUTLET PIPE ONLY A HOLE IN GROUND WILL HAVE TO LOOK AT PLANS. SENT NOV 06.02.2015 | RIP RAP CHANNEL OVERGROWN. CANNOT FIND OUTLET PIPE ONLY A HOLE IN GROUND WILL HAVE TO LOOK AT PLANS. SENT NOV 06.02.2015 |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 5386 | 5386 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-09-30T13:14:57.000Z | 1443618897000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Repair Structural Damage to Riser | Repair Structural Damage to Riser |
| Priority 2 repair recommendations | RISER OR OUTLET STRUCTURE STILL NEEDS TO BE REPLACE. WILL SEND NEXTS NOV. SENT 10.01.2015 | RISER OR OUTLET STRUCTURE STILL NEEDS TO BE REPLACE. WILL SEND NEXTS NOV. SENT 10.01.2015 |
| Vegetation Condition | Yes | Yes |
| Trash Condition | Yes | Yes |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 5619 | 5619 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-07-20T15:04:25.000Z | 1437404665000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Clean Out Trash , Cut Back/Clean Up Overgrown Vegetation , Repair Structural Damage to Inlet(s) | Clean Out Trash , Cut Back/Clean Up Overgrown Vegetation , Repair Structural Damage to Inlet(s) |
| Priority 2 repair recommendations | NO CHANGE FROM PREVIOUS INSPECTION. CALLED MAINT. MANAGER WORK SHOULD START THURSDAY. | NO CHANGE FROM PREVIOUS INSPECTION. CALLED MAINT. MANAGER WORK SHOULD START THURSDAY. |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 5770 | 5770 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-08-28T10:05:42.000Z | 1440756342000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Stabilize at Outlet | Stabilize at Outlet |
| Priority 2 repair recommendations | VEG. MAINT. COMPLETED. NEED TO REPAIR OUTLET PIPE. | VEG. MAINT. COMPLETED. NEED TO REPAIR OUTLET PIPE. |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 6038 | 6038 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-11-25T10:47:24.000Z | 1448448444000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Unacceptable | Unacceptable |
| Priority 1 repair recommendations | Stabilize at Outlet | Stabilize at Outlet |
| Priority 2 repair recommendations | WORK DONE. CALLED CONTRACTOR. ITS TO WET TO WORK. | WORK DONE. CALLED CONTRACTOR. ITS TO WET TO WORK. |
| Fact | Database value | Original source value |
|---|---|---|
| Bmp Id | UER-2822 | UER-2822 |
| Source Record Id | 6054 | 6054 |
| Legacy Asset Id | 2822 | 2822 |
| Inspection date | 2015-12-07T15:08:19.000Z | 1449500899000 |
| Inspection Type | GC Re-Inspection | GC Re-Inspection |
| Overall condition | Acceptable | Acceptable |
| Vegetation Condition | Yes | Yes |
| Sediment Condition | Yes | Yes |
| Trash Condition | Yes | Yes |
| Outlet Condition | Yes | Yes |